Easy to install
Small volume saves space
High cost-effectiveness
No insertion loss
Strong anti-interference ability
The sensor series open-loop Hall current sensor is insulated between primary and secondary and is used to control and measure DC, AC and pulse currents.
The magnetic flux generated by the primary current is gathered in the magnetic circuit and detected by the Hall element in the air gap. The output voltage of the Hall element is processed and the standard voltage signal is output at the output end of the sensor. The voltage signal accurately reflects the change of the primary current.
額定測量電流
IPN(A)
|
測 量 范 圍
IPM(A)
|
交流隔離耐壓有效值
Vd(KV)
@50Hz/60s/0.1mA
|
型 號
|
50 |
0 - ±150
|
3.0 |
YNC-50AT·CB
|
100 |
0 - ±300
|
3.0 |
YNC-100AT·CB
|
200 |
0 - ±600
|
3.0 |
YNC-200AT·CB
|
300 |
0 - ±900
|
3.0 |
YNC-300AT·CB
|
400 |
0 - ±900
|
3.0 |
YNC-400AT·CB
|
500 |
0 - ±900
|
3.0 |
YNC-500AT·CB
|
600 |
0 - ±900
|
3.0 |
YNC-600AT·CB
|
額定測量輸出 VOUT
|
±4V
|
@±IPN
|
負(fù)載電阻 RM
|
≥1 KΩ
≥3 KΩ
|
@ TA = 0℃~70℃
@ TA = -40℃~85℃
|
電源電壓 UC
|
±15V
|
(±5%)
|
電流消耗 IC
|
≤25mA
|
準(zhǔn)確度 X
|
≤±1%FS(+25℃) @IPN
|
線性度 εL
|
≤±0.5%(+25℃) @IPN
|
零點偏移電壓 VOE
|
≤±10mV(+25℃)
|
零點溫度漂移 TCVOE
|
≤±1.0mV/℃ @(-40℃~+85℃)
|
輸出電壓溫度系數(shù) TCVOUT
|
≤0.05%/℃ @(-40℃~+85℃)
|
帶寬(-3db) BW
|
DC...50KHZ
|
響應(yīng)時間 Tr
|
≤3us
|
工作溫度 TA | 儲存溫度 TS | 重量 M |
-40℃~+85℃ | -40℃~+120℃ | 約77g |